Specifications
Model name |
Indoor unit |
FTKG35TV16W |
FTKG50TV16U |
FTKG60TV16U |
Outdoor unit |
RKG35TV16W |
RKG50TV16U |
RKG60TV16U |
Power supply |
1 50Hz 230V |
1 50Hz 230V |
1 50Hz 230V |
(220-240V) |
(220-240V) |
(220-240V) |
|
Power supply intake |
Outdoor unit |
Outdoor unit |
Outdoor unit |
Cooling capacity Rated Full/Half (min.~max.) |
kW |
3.5/1.75(1.75~4.0) |
5.0/2.5 (2.5~5.7) |
6.0/3.0 (2.5~6.7) |
Cooling capacity Rated Full/Half (min.~max.) |
Btu/h |
11900/5970
(6000~13600) |
17100/8500
(8500~19400) |
20500/10240
(8500~22900) |
Power consumption Rated Full/Half (min.~max.) |
W |
999/330 (330-999) |
1415/475 (475-1750) |
1665/580 (580-1665) |
Annual Power consumption |
kWh |
577 |
824 |
989 |
ISEER / Star Rating |
Wh/Wh |
4.70/5* |
4.70/ 5* |
4.70/ 5* |
Voltage Range |
V |
160-265 |
160-265 |
160-265 |
Operating current |
Cooling |
A |
4.67 |
6.37 |
7.4 |
Indoor unit |
Panel colour |
White |
White |
White |
Dimensions HxWxD |
mm |
298 x 800 x 229 |
298 x 885 x 229 |
298 x 885 x 229 |
(Package dimensions) |
mm |
(375 x 895X325) |
(375 x 980 x 325) |
(375 x 980 x 325) |
Weight (Gross) |
kg |
10(14) |
11 (16) |
11 (16) |
Airflow rate *1 X(Y) |
m3/min. |
13.4 (11.9) |
15.4(13.7) |
16.3(14.8) |
Feet3/min (CFM) |
473 (420) |
544(484) |
576(523) |
Operation sound H/M/ML/L/SL |
Cooling |
dBA |
40/36/32/29/26 |
45/42/40/38/35 |
47/45/43/40/38 |
Outdoor unit |
Dimensions (H x W x D) |
mm |
550 x 765 x 285 |
595 x 845 x 300 |
595 x 845 x 300 |
(Package dimensions) |
mm |
(642 x 932 x 380) |
(680 x 1035 x 410) |
(680 x 1035 x 410) |
Weight (Gross) |
kg |
32(38) |
36 (44) |
39(47) |
Operation sound (H) |
Cooling |
dBA |
51 |
54 |
56 |
Breaker size |
A |
15 |
20 |
20 |
Piping length |
Charge-less |
m |
10 |
10 |
10 |
Max. length |
m |
20 |
30 |
30 |
Max. height |
m |
15 |
20 |
20 |
Piping connection |
Gas/Liquid |
mm |
9.5/ 6.4 |
12.7 / 6.4 |
12.7 / 6.4 |
Operation limit |
Cooling |
oCDB |
19.4~50 |
19.4~50 |
19.4~50 |
Measurement conditions:
- Cooling capacity is based on: indoor temp. 27° CDB, 19° CWB; outdoor temp. 35° CDB, piping length 5 m.
- Sound levels are based on temperature conditions 1. above with 5m piping length. These are anechoic conversion values. These values are normally somewhat higher during actual operation as a result of ambient conditions.
Cooling and heating capacities above are rounded off to first decimal. 1TR (Ton of Refrigeration) = ~3.517 kilowatt.
* X(Y) X-Air flow rate during fan operation.
Y-Air flow rate in wet (cooling) condition.
Reviews